型号:FEM51
基本参数
技术参数
|
电子插件FEM51 (AC 2-wire)
Two-wire AC version;
Switch the load directly into the power supply circuit via the thyristor.
Supply voltage: 19...253 V AC
Power consumption: < 1.0 W
Residual current consumption (IR): < 4 mA; 5.5 mA for short fork (in switch-off moment < 1 mA for 100 ms)
Short-circuit protection
Separation voltage: 3.7 kV
FEM51 overvoltage protection: overvoltage category III
Two-wire AC connection
Always connect in series with a load!
Check the following:
• the residual current consumption in blocked state
• that for low voltage
– the voltage drop across the load is such that the minimum terminal voltage at the electronic insert (19 V) when blocked is not undershot.
– the voltage drop across the electronics when switched through is observed (up to 12 V)
• that a relay cannot de-energise with holding power below 1 mA.
If this is the case, a resistor should be connected parallel to the relay (RC module available on request).
• When selecting the relay, pay attention to the holding power / rated power
(See below "Connectable load")
Signal on alarm
Output signal on power failure or in the event of device failure: IR
• For relays with a minimum holding power/rated power > 2.5 VA at 253 V (10 mA) or > 0.5 VA at 24 V (20 mA)
• Relays with a lower holding power/rated power can be operated by means of an RC module connected in parallel
• For relays with a maximum holding power/rated power < 89 VA at 253 V or 8.4 VA at 24 V
• Voltage drop across FEM51 max. 12 V
• Residual current with blocked thyristor max. 4 mA (5.5 mA for short fork)
• Load current max. 350 mA (short-circuit proof)